Reference-based what this means

Tube-bank cross-flow heat transfer for superheated steam — same Zukauskas (1972) gas-side convection and Hottel radiation engine as Screen Tube, but the tube side is single-phase superheated steam (no boiling, standard Dittus-Boelter both sides). Applies equally to Reheaters — same physics.

? New here? How to use this calculator

What this answers: Required tube surface to raise saturated steam to its final superheated temperature.

The numbers already in the fields are a complete, working example — not a template you must match. Overwrite any of them with your own design's values; the results update as you type.

Unfamiliar term? Look for a ? next to a field label, or browse the full Glossary.

Flue Gas (from Temperature Profile)
kg/hr
°C
°C
bar
Gas Composition (mol%, wet basis)
Tube Bank Geometry
mm — 1st Superheater
mm
mm
mm
gas-flow-direction row count — for the Zukauskas row-correction factor ONLY. Different from Total Tubes (below) which sets steam velocity.
per panel
panels in the bank
m — full serpentine developed length (NOT simple chamber height)
m
m — net open height, tubes already subtracted
mm — bare tube bank (not membrane wall), commercial-steel range
Steam Side
kg/hr — this stage's own flow, not total boiler output
°C — ≈T_sat, enters saturated from drum for the first SH stage
°C — solved from energy balance + pressure drop; this is just the iteration starting point
barg — near drum pressure, minimal drop yet at first SH stage
bar — at the boiler's installation site
mm
Tube Wall & Fouling?
W/m·K
micron
W/m·K
% of gas-side Q — typical 1.5-3%

Duty

Heat Transfer Coefficients?

Pressure Drop

Heating Surface?

Radiation: same Hottel-type engine as Furnace/Screen Tube, Mean Radiating Length via L=Factor×(Pitch−D). Gas-side convection: Zukauskas (1972), same branch logic and digitized row-correction table as Screen Tube. Steam side: single-phase Dittus-Boelter both directions (no boiling — steam here is already superheated, no phase change), properties averaged inlet/outlet. Ao=π×OD×L×N, Ai=π×ID×L×N (individual tubes with gaps, not a membrane wall). Tube count sets steam velocity (see the guidance panel); tube length is what reconciles Actual vs Required heating surface — the same two-variable relationship as Furnace's tube-length solve. Pressure drop: gas-side uses a Jakob-type tube-bank friction-factor correlation; steam-side uses standard single-phase Darcy-Weisbach (Colebrook) plus elevation, no two-phase terms needed.