Combustion & Emissions / Reference Properties
Cp, density, thermal conductivity, and viscosity for individual flue gas species (CO2, H2O, O2, N2, SO2, plus CO/H2/CH4/Air) and their mixture at any composition and temperature — pure gas properties, no furnace geometry needed.
What this answers: Cp, density, conductivity and viscosity for flue gas species and mixtures, at any composition and temperature — the property engine other modules build on.
The numbers already in the fields are a complete, working example — not a template you must match. Overwrite any of them with your own design's values; the results update as you type.
Unfamiliar term? Look for a ? next to a field label, or browse the full Glossary.
| Species | Cp (kJ/kg·K) | μ (μPa·s) | k (W/m·K) |
|---|
Correlation: rational-polynomial-in-log(pL) fit to modern spectroscopic (HITEMP-based) data — more accurate than classic Hottel charts or Leckner's polynomials, per literature comparisons (Hottel >200% error, Leckner -90%/+180%, this class of correlation ~0.7% average error vs line-by-line reference). Mean Beam Length L=3.5×V/A (Hottel's geometric approximation for an enclosure). CO2 and H2O each use a temperature-dependent branch (<1100K / ≥1100K) selected automatically by the actual flue gas temperature.
Quick reaction — was this calculator useful?
Was this calculator useful? Tell us what's missing or what you'd like to see next.