Boiler Heat Transfer Train / Steam Temperature Control
Spray attemperation between Superheater stages — high-pressure spray water (from the Deaerator, via the feed pump) mixes with steam from the Primary/1st Superheater at a purpose-built mixing header. Solved by enthalpy mixing: h_mix=(ṁ_steam·h_steam+ṁ_spray·h_spray)/(ṁ_steam+ṁ_spray), then T_mix is recovered by inverting the steam table at (h_mix, P_mix). Includes a live check that spray pressure exceeds steam pressure by the standard 10+ bar margin needed for complete atomization/mixing.
What this answers: How much a spray of water cools superheated steam, and whether the spray pressure is high enough to actually mix in properly.
The numbers already in the fields are a complete, working example — not a template you must match. Overwrite any of them with your own design's values; the results update as you type.