PlantAISim

Boiler Heat Transfer Train / Tube Bank

Air Preheater

Reference-based what this means

A tubular air preheater with the physics flipped from every other tube-bank module: flue gas flows INSIDE the tubes (Dittus-Boelter convection + in-pipe Hottel radiation), while combustion air flows OUTSIDE in crossflow (same Zukauskas engine as Screen Tube/Superheater, applied to air instead of flue gas). No phase change on either side. The overall U formula keeps flue gas as the unscaled first term and air as the Ao/Ai-scaled term — the same convention used everywhere else in this project, even though the physical inside/outside has swapped.

? New here? How to use this calculator

What this answers: How much tube surface an air preheater needs to warm combustion air using the last heat left in the flue gas, before it goes to the stack.

The numbers already in the fields are a complete, working example — not a template you must match. Overwrite any of them with your own design's values; the results update as you type.

Unfamiliar term? Look for a ? next to a field label, or browse the full Glossary.

Flue Gas (inside tubes, from Temperature Profile)
kg/hr
°C
°C
bar
Flue Gas Composition (mol%, wet basis)
Combustion Air (outside tubes, crossflow)
kg/hr
°C
°C
°C — for humidity ratio calculation
% — humidity ratio (ω) is computed from these and normalized into the mixture
Tube Bank Geometry
mm
mm
mm
mm
row-correction factor is looked up automatically below
m
m — net open width for air crossflow
m — same as tube length in this design
Site Reference
barg — reference only, not used in this module's own physics
bar
Tube Wall & Fouling?
W/m·K
micron — on the air/outer side, following the convention of the reference design calculation
W/m·K
mm — commercial steel tube, typical
% of gas-side Q — typical 1.5-3%

Duty

Heat Transfer Coefficients?

Pressure Drop

Heating Surface?

Radiation: same Hottel-type engine as Furnace/Flue Gas Thermal Properties, but Mean Radiating Length uses the tube-bank form L=Factor×(Pitch−D) instead of 3.5×V/A. Convection: Zukauskas (1972) — V_max from the free-stream velocity via an arrangement-dependent factor, Re_max on that velocity, C1/m coefficients depending on Re_max range and ST/SL ratio, with a row-count correction factor. Ao=π×OD×L×N and Ai=π×ID×L×N (full circumference both sides — individual tubes with gaps, unlike Furnace's membrane wall where only Ao uses the full diameter and Ai is halved). Inlet dryness fraction is a direct input since Screen Tube commonly receives already-partially-evaporated flow rather than starting from saturated liquid. This module reports Actual (from your tube-length input) vs Required (from U×LMTD) heating surface as a Rating check.

Quick reaction — was this calculator useful?

Was this calculator useful? Tell us what's missing or what you'd like to see next.

Send Feedback